Szczegóły publikacji

Opis bibliograficzny

Adsorption chiller in a combined heating and cooling system: simulation and optimization by neural networks / Jarosław Krzywanski, Karol SZTEKLER, Marcin Bugaj, Wojciech KALAWA, Karolina Grabowska, Patryk Robert Chaja, Marcin Sosnowski, Wojciech NOWAK, Łukasz MIKA, Sebastian Bykuć // Bulletin of the Polish Academy of Sciences. Technical Sciences ; ISSN 0239-7528. — 2021 — vol. 69 no. 3 art. no. e137054, s. 1-11. — Bibliogr. s. 9-11, Abstr. — Publikacja dostępna online od: 2021-06

Autorzy (10)

Słowa kluczowe

soft computingartificial neural networksadsorption heat pumpscooling capacitypolygenerationlow grade thermal energy

Dane bibliometryczne

ID BaDAP134990
Data dodania do BaDAP2021-07-05
Tekst źródłowyURL
DOI10.24425/bpasts.2021.137054
Rok publikacji2021
Typ publikacjiartykuł w czasopiśmie
Otwarty dostęptak
Creative Commons
Czasopismo/seriaBulletin of the Polish Academy of Sciences, Technical Sciences

Abstract

Adsorption cooling and desalination technologies have recently received more attention. Adsorption chillers, using eco-friendly refrigerants, provide promising abilities for low-grade waste heat recovery and utilization, especially renewable and waste heat of the near ambient temperature. However, due to the low coefficient of performance (COP) and cooling capacity (CC) of the chillers, they have not been widely commercialized. Although operating in combined heating and cooling (HC) systems, adsorption chillers allow more efficient conversion and management of low-grade sources of thermal energy, their operation is still not sufficiently recognized, and the improvement of their performance is still a challenging task. The paper introduces an artificial intelligence (AI) approach for the optimization study of a two-bed adsorption chiller operating in an existing combined HC system, driven by low-temperature heat from cogeneration. Artificial neural networks are employed to develop a model that allows estimating the behavior of the chiller. Two crucial energy efficiency and performance indicators of the adsorption chiller, i.e., CC and the COP, are examined during the study for different operating sceneries and a wide range of operating conditions. Thus this work provides useful guidance for the operating conditions of the adsorption chiller integrated into the HC system. For the considered range of input parameters, the highest CC and COP are equal to 12.7 and 0.65 kW, respectively. The developed model, based on the neurocomputing approach, constitutes an easy-to-use and powerful optimization tool for the adsorption chiller operating in the complex HC system.

Publikacje, które mogą Cię zainteresować

artykuł
#118768Data dodania: 10.1.2019
Optimization of a three-bed adsorption chiller by genetic algorithms and neural networks / J. Krzywanski, K. Grabowska, F. Herman, P. Pyrka, M. Sosnowski, T. Prauzner, W. NOWAK // Energy Conversion and Management ; ISSN 0196-8904. — 2017 — vol. 153, s. 313–322. — Bibliogr. s. 321–322, Abstr. — Publikacja dostępna online od: 2017-10-13
artykuł
#42710Data dodania: 20.1.2009
Queueing systems and networks : models and applications / B. FILIPOWICZ, J. KWIECIEŃ // Bulletin of the Polish Academy of Sciences. Technical Sciences ; ISSN 0239-7528. — 2008 — vol. 56 no. 4 spec. iss.: Dynamic systems, stability, controllability, and automatic control : dedicated to Professor Henryk Gorecki, s. 379–390. — Bibliogr. s. 390, Abstr. — Zastosowano procedurę peer review