An indicator for assessing the hosting capacity of low-voltage power networks for distributed energy resources / Grzegorz Hołdyński, Zbigniew Skibko, Andrzej FIRLIT // Energies [Dokument elektroniczny]. — Czasopismo elektroniczne ; ISSN 1996-1073 . — 2025 — vol. 18 iss. 23 art. no. 6315, s. 1–16. — Wymagania systemowe: Adobe Reader. — Bibliogr. s. 14–16, Abstr. — Publikacja dostępna online od: 2025-11-30
Autorzy (3)
- Hołdyński Grzegorz
- Skibko Zbigniew
- AGHFirlit Andrzej
Słowa kluczowe
Dane bibliometryczne
| ID BaDAP | 164992 |
|---|---|
| Data dodania do BaDAP | 2026-01-09 |
| Tekst źródłowy | URL |
| DOI | 10.3390/en18236315 |
| Rok publikacji | 2025 |
| Typ publikacji | artykuł w czasopiśmie |
| Otwarty dostęp | |
| Creative Commons | |
| Czasopismo/seria | Energies |
Abstract
The article analyses the hosting capacity of low-voltage (LV) power grids for connecting distributed energy sources (DER), mainly photovoltaic installations (PV), considering technical limitations imposed by power system operating conditions. The main objective of the research was to develop a simple equation that enables the quick estimation of the maximum power of an energy source that can be safely connected at a given point in the network without causing excessive voltage rise or overloading the transformer and line cable. The analysis was performed on the basis of relevant calculation formulas and simulations carried out in DIgSILENT PowerFactory, where a representative low-voltage grid model was developed. The network model included four transformer power ratings (40, 63, 100, and 160 kVA) and four cable cross-sections (25, 35, 50, and 70 mm2), which made it possible to assess the impact of these parameters on grid hosting capacity as a function of the distance from the transformer station. Based on this, the PHCI indicator was developed to determine the hosting capacity of a low-voltage network, using only the transformer rating and the length and cross-section of the line for the calculations. A comparison of the results obtained using the proposed equation with detailed calculations showed that the approximation error does not exceed 15%, which confirms the high accuracy and practical applicability of the proposed approach.