CFD analysis of elements of an adsorption chiller with desalination function / Karol SZTEKLER, Tomasz SIWEK, Wojciech KALAWA, Łukasz LIS, Łukasz MIKA, Ewelina RADOMSKA, Wojciech NOWAK // W: Adsorption desalination and cooling systems: advances in design, modeling and performance / eds. Jaroslaw Krzywanski, Norbert Skoczylas, Marcin Sosnowski. — Basel : MDPI, cop. 2022. — N. Skoczylas - afiliacja: The Strata Mechanics Research Institute of the Polish Academy of Sciences. — ISBN: 978-3-0365-5913-1; e-ISBN: 978-3-0365-5914-8. — S. 215–233. — Bibliogr. s. 232–233, Abstr. — Reprinted from: Energies 2021, 14, 7804, doi.org/10.3390/en14227804

Autorzy (7)

Słowa kluczowe

adsorptiondesalinationchillerCFD

Dane bibliometryczne

ID BaDAP143943
Data dodania do BaDAP2022-12-21
Tekst źródłowyURL
Rok publikacji2022
Typ publikacjifragment książki
Otwarty dostęptak
Creative Commons

Abstract

This paper presents the results of numerical tests on the elements of an adsorption chiller that comprises a sorption chamber with a bed, a condenser, and an evaporator. The simulation is based on the data and geometry of a prototype refrigeration appliance. The simulation of this problem is unique and has not yet been performed, and so far, no simulation of the phenomena occurring in the systems on a real scale has been carried out. The presented results are part of the research covering the entire spectrum of designing an adsorption chiller. The full process of numerical modeling of thermal and flow phenomena taking place in the abovementioned components is presented. The computational mesh sensitivity analysis combined in the k-ε turbulence model was performed. To verify and validate the numerical results obtained, they were compared with the results of tests carried out on a laboratory stand at the AGH Center of Energy. The results of numerical calculations are in good agreement with the results of the experimental tests. The maximum deviation between the pressure obtained experimentally and by simulations is 1.8%, while for temperatures this deviation is no more than 0.5%. The results allow the identification of problems and their sources, which allows for future structural modifications to optimize the operation of the device.

Publikacje, które mogą Cię zainteresować

fragment książki
#143938Data dodania: 21.12.2022
Optimisation of operation of adsorption chiller with desalination function / Karol SZTEKLER // W: Adsorption desalination and cooling systems: advances in design, modeling and performance / eds. Jaroslaw Krzywanski, Norbert Skoczylas, Marcin Sosnowski. — Basel : MDPI, cop. 2022. — N. Skoczylas - afiliacja: The Strata Mechanics Research Institute of the Polish Academy of Sciences. — ISBN: 978-3-0365-5913-1; e-ISBN: 978-3-0365-5914-8. — S. 67–86. — Bibliogr. s. 85–86, Abstr. — Reprint from: Energies 2021, 14, 2668, doi.org/10.3390/en14092668
fragment książki
#143941Data dodania: 21.12.2022
The effects of using steam to preheat the beds of an adsorption chiller with desalination function / Karol SZTEKLER, Wojciech KALAWA, Łukasz MIKA, Łukasz LIS, Ewelina RADOMSKA, Wojciech NOWAK // W: Adsorption desalination and cooling systems: advances in design, modeling and performance / eds. Jaroslaw Krzywanski, Norbert Skoczylas, Marcin Sosnowski. — Basel : MDPI, cop. 2022. — N. Skoczylas - afiliacja: The Strata Mechanics Research Institute of the Polish Academy of Sciences. — ISBN: 978-3-0365-5913-1; e-ISBN: 978-3-0365-5914-8. — S. 171–186. — Bibliogr. s. 185–186, Abstr. — Reprinted from: Energies 2021, 14, 6454, doi.org/10.3390/en14206454